Plan Review Notes For Permit 03100205 |
Permit Number |
03100205 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-16 00:00:00 | UNSAT | | ~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THERE ARE SEVERAL VIOLATIONS OF | | RECEPTACLE SPACING PER 210.52(A)(1) & | | (2) IN THE EXERCISE,STUDY,ENTRY AND | | BEDROOMS 2 & 3. | | | | 2} THE KITCHEN NEEDS RECEPTACLES ADDED | | TO COMPLY WITH 210.52(C)(1). | | | | 3} THE NOTE REGARDING THE SMOKE | | DETECTORS SHOULD BE CHANGED TO READ | | "BED ROOM" CIRCUIT PER 210.12 2002 NEC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|