Plan Review Notes
Plan Review Notes For Permit 03100205
Permit Number 03100205
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-16 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE SEVERAL VIOLATIONS OF
 RECEPTACLE SPACING PER 210.52(A)(1) &
 (2) IN THE EXERCISE,STUDY,ENTRY AND
 BEDROOMS 2 & 3.
  
 2} THE KITCHEN NEEDS RECEPTACLES ADDED
 TO COMPLY WITH 210.52(C)(1).
  
 3} THE NOTE REGARDING THE SMOKE
 DETECTORS SHOULD BE CHANGED TO READ
 "BED ROOM" CIRCUIT PER 210.12 2002 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718