2003-11-25 00:00:00BUILDING REVIEW CHECKLIST:
 1-PLANS DON'T MATCH. ELECTRICAL PLAN
 DOESN'T MATCH FLOOR PLAN. CLARIFY AS
 REQUIRED.
 2-ENERGY CALCULATIONS DON'T MATCH FLOOR
 PLAN AREA. PLANS SHOW 1400S.F. AND
 ENERGY CALCS SHOW 1092S.F. CLARIFY
 AS REQUIRED.
 3-PROVIDE IMPACT FEES PAID RECEIPT.
 4-PROVIDE COMPLETE INFORMATION FOR STORM
 SHUTTERS. INSTALLATION SCHEDULE KEY
 PLAN & CLEARLY MARK ON DWGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE
 AND SPACING TO BE USED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 **NOTE: IF INFORMATION IS NOT COMPLETE,
 THEN, CONTRACTOR MAY APPLY FOR STORM
 SHUTTERS UNDER A SEPARATE PERMIT.
 5-CONTRACTOR TO UPDATE INSURANCE.