Date |
Text |
2003-10-20 00:00:00 | ************ UNSAT ************** |
| |
| 1)NOTE: PLEASE SEE PLANS REFERENCE 1999 |
| NEC, AS OF 7/1/2003 WE ARE NOW UNDER |
| THE 2002 NEC. |
| |
| 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT |
| PROTECTED CIRCUITS PER 210.12. |
| PLEASE SEE THAT IS IT NO LONGER JUST |
| RECEPTS. |
| |
| 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM |
| COMPLETE WITH CONDUCTORS/CONDUITS AND |
| LOAD CALCULATIONS FOR MIN REQ'D PER |
| NEC 220. 215.5MIN LOADS PER NEC 220 |
| |
| 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE |
| SYSTEM PER 250.50. |
| |
| 5)NOTE: PLEASE CLARIFY REQ'D SD'S PER |
| NFPA-72 2-5. PLEASE SEE THAT PLANS SHOW |
| WHAT APPEAR TO BE TELEPHONE OUTLETS |
| AT LOCATIONS FOR SD'S? |
| |
| 6)NOTE: PLEASE SHOW A/C UNITS AND RECEPT |
| -S PER 210.63. |
| |
| 7)NOTE: PLEASE SEE MISSING RECEPT FOR |
| 2' OF WALL SPACE PER 210.52. BR#3 |
| |
| 8)NOTE: PLEASE SEE FS 471.025 AND FAC |
| 61G15-23.002. PLANS ARE REQ'D TO BE |
| ORIGINAL SIGNATURE,DATED AND SEALED BY |
| ENGINEER OF RECORD. THIS COMMENT IS |
| FOR ALL PAGES INCLUSIVE OF OTHER TRADES |
| ALSO,WEATHER OR NOT IT IS ANOTHER REVIEW |
| -ERS COMMENTS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |