2003-10-20 00:00:00************ UNSAT **************
  
 1)NOTE: PLEASE SEE PLANS REFERENCE 1999
 NEC, AS OF 7/1/2003 WE ARE NOW UNDER
 THE 2002 NEC.
  
 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 210.12.
 PLEASE SEE THAT IS IT NO LONGER JUST
 RECEPTS.
  
 3)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 COMPLETE WITH CONDUCTORS/CONDUITS AND
 LOAD CALCULATIONS FOR MIN REQ'D PER
 NEC 220. 215.5MIN LOADS PER NEC 220
  
 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM PER 250.50.
  
 5)NOTE: PLEASE CLARIFY REQ'D SD'S PER
 NFPA-72 2-5. PLEASE SEE THAT PLANS SHOW
 WHAT APPEAR TO BE TELEPHONE OUTLETS
 AT LOCATIONS FOR SD'S?
  
 6)NOTE: PLEASE SHOW A/C UNITS AND RECEPT
 -S PER 210.63.
  
 7)NOTE: PLEASE SEE MISSING RECEPT FOR
 2' OF WALL SPACE PER 210.52. BR#3
  
 8)NOTE: PLEASE SEE FS 471.025 AND FAC
 61G15-23.002. PLANS ARE REQ'D TO BE
 ORIGINAL SIGNATURE,DATED AND SEALED BY
 ENGINEER OF RECORD. THIS COMMENT IS
 FOR ALL PAGES INCLUSIVE OF OTHER TRADES
 ALSO,WEATHER OR NOT IT IS ANOTHER REVIEW
 -ERS COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  