Plan Review Notes
Plan Review Notes For Permit 03092071
Permit Number 03092071
Review Stop B
Sequence Number 1
Notes
Date Text
2003-10-29 00:00:00BUILDING CHECKLIST:
 1-PLANS DON'T MATCH. PLANS SUBMITTED ARE
 FOR 2 DIFFERENT MODELS.
 2-NEED LETTER CERTIFICATE FROM THE THIRD
 PARTY AGENCY AS REQ'D BY SEC. 428.4.2
 FBC 2001.
 3-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS & RECEIPT.
 4-SURVEY NEEDS ORIGINAL SIGNATURE, DATE
 AS REQ'D BY CHAPTER 471 FL STATUTES.
 5-ENERGY CALCULATIONS: A)COMPLETE ALL
 INFO. ON TOP OF FORM.
 B)CLARIFY WHY THERE IS NOT INSULATION ON
 THE RAISED FLOOR . SECTION 605 CHAPTER
 13 FBC 2001.
 C)REVISE/CLARIFY VALUE GIVEN FOR UNDER
 ATTIC INSULATION. SEE PLANS FOR RVALUE
 USED.
 D)PREPARER TO SIGN AND DATE BOTTOM OF
 FORM. SEC. 103.1.1 CHAPTER 13 FBC.
 E)OWNER/AGENT TO SIGN AND DATE BOTTOM OF
 FORM. SEC. 103.1.2 CHAPTER 13 FBC 2001
  
 6-LOCAL ENGINEER TO PROVIDE ALL INFO. AS
 LISTED ON SEC. 1606.1.7 FBC 2001.
 7-LOCAL ENGINEER TO PROVIDE ALL HIS INFO
 AS REQ'D BY CHAPTER 471 FL. STATUTES.
 8-STORM SHUTTERS: A)PROVIDE LEGIBLE AND
 COMPLETE DRAWINGS. PAGE ONE AND TWO.
 B)PROVIDE KEY PLAN AND COMPLETE INSTALLA
 TION SCHEDULE.
 C)CLEARLY MARK ON STORM SHUTTER DRAWINGS
 SPECIFIC MOUNTING CONDITIONS & ANCHOR
 TYPE AND SPACING TO BE USED ACCORDING
 TO THE DESIGN PRESSURES, PANEL SPAN,
 EDGE DISTANCE, CONNECTION TYPE AND
 STRUCTURE TO BE ATTACHED TO. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 9-SOIL TEST REPORT TO HAVE ORIGINAL
 SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES.
 10-CONTRACTOR'S SCREEN CALLS FOR EXPIRED
 INSURANCE. PLEASE, UPDATE CONTRACTOR'S
 INFORMATION WITH PERMIT CLERK.
 11-OWES $171.51 FOR UPDATED VALUE AND
 RADON FEES. PLEASE PAY ATTACHED
 RECEIPT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.