Plan Review Notes For Permit 03092027 |
Permit Number |
03092027 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-23 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT 1 WATER RISER DIAGRAM, SHUT OFF | | VALVES REQUIRED FOR HOSE BIBBS. SECTION | | 606.2(2). | | 2) SHT 1 SANT. RISER DIAGRAM, WATER | | CLOSETS ARE NOT VENTED. SEE RED LINE | | CORRECTION ON PLANS. | | 3) SUBMIT CALCULATIONS FOR ROOF GUTTER | | AND DOWNSPOUTS. SHOW SQUARE FOOTAGE OF | | ROOF & SHOW 1/2 AREA OF ALL VERTICAL | | WALLS INCLUDING PARAPETS INCLUDED IN | | CALCULATIONS. SHOW SIZE OF GUTTER AND | | DOWNSPOUTS. INDICATE SLOPE OF GUTTER AND | | SHOW HOW GUTTER IS SLOPED ON PLANS. | | TABLE 1106.6 | | 4) TABLE 403.1 REQUIRES A DRINKING | | FOUNTAIN IN EACH SPACE. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|