Date Text
2003-10-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT 1 WATER RISER DIAGRAM, SHUT OFF
 VALVES REQUIRED FOR HOSE BIBBS. SECTION
 606.2(2).
 2) SHT 1 SANT. RISER DIAGRAM, WATER
 CLOSETS ARE NOT VENTED. SEE RED LINE
 CORRECTION ON PLANS.
 3) SUBMIT CALCULATIONS FOR ROOF GUTTER
 AND DOWNSPOUTS. SHOW SQUARE FOOTAGE OF
 ROOF & SHOW 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS INCLUDED IN
 CALCULATIONS. SHOW SIZE OF GUTTER AND
 DOWNSPOUTS. INDICATE SLOPE OF GUTTER AND
 SHOW HOW GUTTER IS SLOPED ON PLANS.
 TABLE 1106.6
 4) TABLE 403.1 REQUIRES A DRINKING
 FOUNTAIN IN EACH SPACE.
  