Plan Review Notes
Plan Review Notes For Permit 03092027
Permit Number 03092027
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-14 00:00:00********** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS,PANELS, BRKRS ALL MUST BE RATED
 FOR THE AVAILABLE FAULT CURRNET.
 110.9/215.5
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS. 700.12E
  
 3)NOTE: PLEASE CLARIFY SIZE OF SEC'S
 AS THE NOTE DOES NOT APPEAR TO BE ON
 RISER? PLEASE CLARIFY SIZE OF SERVICE,
 375?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]