Plan Review Notes For Permit 03092020 |
Permit Number |
03092020 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-28 00:00:00 | 1) TEMPORARY PARTITIONS WHEN ERECTED | | SHALL NOT INTERFERE WITH ANY EXISTING | | FIRE PROTECTION EQUIPMENT. | | | | 2) DECORATIVE EIFS STILL SHOWN ON SOME | | OF THE DRAWINGS. PLEASE SEE APPENDIX F. | | | | 3) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM REMODEL. | | | | 4) POWER OPERATED DOORS NEAR PORTE | | COCHERE MUST COMPLY WITH POWER | | OPERATED DOORS AND HAVE BREAK-AWAY | | FEATURES. | | | | 5) FIRE HEAD ON PAGE MFP-252 DISPLAYS | | A DOOR BLOCKING A SPRINKLER HEAD, SUITE | | TYPE 1. | | | | 6) PROVIDE SEPARATE PLANS AND PERMITS | | FOR FIRE SPRINKLER REMODEL. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|