Notes |
Date |
Text |
2003-10-28 00:00:00 | 1) PLEASE EXPLAIN RATIONALE ON | | UNDERCUTTING ALL GUESTROOM ENTRY DOORS | | ON PAGE A0.20. | | | | 2) DECORATIVE EIFS STILL SHOWN ON | | ELEVATION DRAWINGS AND ON OTHER PLANS. | | PLEASE SEE APPENDIX F, ARCHITECTURAL | | TRIM LOCATED IN THE FIRE LIMITS. | | | | 3) BUILDING ADDRESS REQUIRED. | | | | 4) SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | 5) PROVIDE SEPARATE PLANS AND PERMITS | | FOR NEW BASE BUILDING AUDIO/VISUAL | | DEVICES PLANNED FOR HOTEL ROOMS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|