Plan Review Notes
Plan Review Notes For Permit 03092018
Permit Number 03092018
Review Stop P
Sequence Number 1
Notes
Date Text
2003-10-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHTS A/060 & A/061 DEMO NOTE #11, ALL
 CAPPED PLUMBING LINES SHALL BE INSPECTED
 PRIOR TO COVERING.
 2) SHT A/100 WOMENS TOILET ROOM #027,
 WHERE 6 OR MORE STALLS ARE PROVIDED, IN
 ADDITION TO THE STALL COMPLYING WITH 11-
 4.17.3, AT LEAST ONE STALL 36" WIDE WITH
 AN OUTWARD SWINGING, SELF-CLOSING DOOR
 AND PARALLEL GRAAB BARS COMPLYING WITH
 FIG. 30(D) AND 11-4.16 SHALL BE PROVIDED
 3) SHT K-2 PLUMBING NOTES #2 - CONTACT
 RODNEY COMPO, ENVIRONMENTAL COMPLIANCE
 FOR SIZE OF GREASE INTERCEPTOR. UTILITY
 ORD. #29389-96. (561) 837-4074
 4) PLANS SHALL BE ROUTED TO THE DEPART-
 MENT OF BUSINESS REGULATION HOTEL AND
 RESTAURANT DIVISION FOR REVIEW PRIOR TO
 SUBMITTING TO CITY FOR PLAN REVIEW. ALL
 REVIEW/WORK SHEETS SHALL ACCOMPANY THE
 PLANS FOR REVIEW. (954) 958-5520
 SECTION 101.4.7
 5) SHTS MP060, MP061, & MP100 ALL CAPPED
 PLUMBING LINES TO BE INSPECTED PRIOR TO
 COVERING.
 6) SHT MP 301 ALL WATER RISER DIAGRAMS,
 ALL WATER HAMMER ARRESTORS SHALL BE LO-
 CATED NEAR THE FIXTURES IN AN "EFFECTIVE
 RANGE" NOT IN THE CEILING AS SHOWN. PDI-
 WH 201 AND MANUF. INSTALLATION INSTRUCT-
 IONS. UNLESS BOTH WASH MACHINES ARE ON A
 COMMON DROP, BOTH WASH MACHINES WILL RE-
 QUIRE A WATER HAMMER ARRESTOR.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]