2003-10-21 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM.
 SHOWS FEED TO NEW HV-1 AS 400A AND NOTE
 MENTIONS NEW 200A??
  
 2)NOTE: PLEASE ALSO SHOW GROUNDING
 ATTACHMENT PER 250.30 FOR TRANSFORMERS.
  
 3)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 FOR ADDITION OF NEW EQUIPMENT TO EXIST-
 -ING MDP-1. 215.5/220
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AFFECT ON ELECTRICAL PLANS
  
  
 PLEASE SUBMITTHE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]