Plan Review Notes For Permit 03092018 |
Permit Number |
03092018 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-21 00:00:00 | ************** UNSAT ************** | | | | 1)NOTE: PLEASE CORRELATE RISER DIAGRAM. | | SHOWS FEED TO NEW HV-1 AS 400A AND NOTE | | MENTIONS NEW 200A?? | | | | 2)NOTE: PLEASE ALSO SHOW GROUNDING | | ATTACHMENT PER 250.30 FOR TRANSFORMERS. | | | | 3)NOTE: PLEASE PROVIDE LOAD CALCULATIONS | | FOR ADDITION OF NEW EQUIPMENT TO EXIST- | | -ING MDP-1. 215.5/220 | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | THAT MAY HAVE AFFECT ON ELECTRICAL PLANS | | | | | | PLEASE SUBMITTHE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|