2003-10-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03092017PHASE 1B
 ADD: 630 CLEARWATER PARK DR
 8TH & 7TH FLOORS
 CONT: WHITING-TURNER CONT CO
 TEL: (954)776-0880
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 MISSING ALL PRODUCT APPROVALS!!!!!!!!!!
  
 2)EFIS SYSTEM EXTERIOR WALL COVERINGS:
 ARE TO COMPLY WITH 2603.(1-7)
 (1) PROVIDING TESTING ON ACCORDANCE WITH
 ASTM E 119
 (2) THERMAL BARRIER
 (3) POTENIAL HEAT
 (4) FLAME SPREAD/ SMOKE DEVELOPMENT
 (5) TEST STANDARD
 (6) LABEL REQUIRED
 (7) IGNITION
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026