Plan Review Notes
Plan Review Notes For Permit 03091830
Permit Number 03091830
Review Stop M
Sequence Number 3
Notes
Date Text
2003-12-18 00:00:00DENIED:
  
 1.FORM 600C SUBMITTED FOR THE ADDITION
 TO THE EXISTING RESIDENCE DOES INDICATES
 561 SQ FT.THE MANUAL J REFLECTS SYSTEM
 1 INDICATES THE TOTAL EQUIPMENT LOAD
 WILL BE APPROXIMATELY 2 TONS.THE PLAN
 INDICATES A 4 TON UNIT.IF THE 4 TON
 IS EXISTING PLEASE INDICATE THIS ON THE
 FORM 600C.SHOULD SYSTEM 1 BE A NEW
 INSTALLATION, PLEASE PROVIDE ENERGY &
 MANUAL J CALCULATIONS BASED UPON METHOD
 A OF THE 2001 FBC CHAPTER 13 SUBCHAPTER
 600.
  
 2.THE ENERGY CALCULATIONS FOR THE
 ACCESSORY BUILDING INDICATES 387 SQ FT
 OF CONDITIONED SPACE, REQUIRING A 2 TON
 UNIT.THE EQUIPMENT SCHEDULE ON M-1
 SHOWS A 3 TON UNIT.PLEASE REVISE PLAN
 TO MATCH THE ENERGY CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.