2003-12-09 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REVISE THE PLANS TO SHOW THE
 FOLLOWING FOR CODE COMPLIANCE AND
 RESUBMIT PRIOR TO CALLING FOR
 ELECTRICAL INSPECTION.
  
 1} SHOW THE LOCATION OF THE SERVICE
 DISCONNECTS AND GUTTER ON THE
 PLANS.MUST COMPLY WITH 110.26.
  
 2} PANEL "B" MUST HAVE A DISCONNECTING
 MEANS AT THE BUILDING PER 225.30.PLEASE
 SHOW SAME.
  
 3} THE BATH ROOM UNDER THE STAIRWELL IN
 THE EXISTING HOUSE MUST COMPLY WITH 210.
 52(D) FOR RECEPTACLE PLACEMENT IF THERE
 IS WORK IN THAT AREA.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  