2003-12-09 00:00:00 | | | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | PLEASE REVISE THE PLANS TO SHOW THE | | FOLLOWING FOR CODE COMPLIANCE AND | | RESUBMIT PRIOR TO CALLING FOR | | ELECTRICAL INSPECTION. | | | | 1} SHOW THE LOCATION OF THE SERVICE | | DISCONNECTS AND GUTTER ON THE | | PLANS.MUST COMPLY WITH 110.26. | | | | 2} PANEL "B" MUST HAVE A DISCONNECTING | | MEANS AT THE BUILDING PER 225.30.PLEASE | | SHOW SAME. | | | | 3} THE BATH ROOM UNDER THE STAIRWELL IN | | THE EXISTING HOUSE MUST COMPLY WITH 210. | | 52(D) FOR RECEPTACLE PLACEMENT IF THERE | | IS WORK IN THAT AREA. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|