Plan Review Notes
Plan Review Notes For Permit 03091830
Permit Number 03091830
Review Stop M
Sequence Number 2
Notes
Date Text
2003-11-17 00:00:00DENIED:
 1.ENERGY CALCULATIONS SUBMITTED
 INDICATE 1 SYSTEM, 15 SEER.PLANS
 INDICATE TWO SYSTEMS AT 12.1 SEER. FORM
 600C SUBMITTED FOR SYSTEM 1 AT 12.1
 SEER. PLEASE CORRELATE ENERGY CALCS AND
 MANUAL J CALCS.
  
 2.AUXILIARY DRAIN PANS REQUIRED AS PER
 2001 FBC(M) 307.2.3.
  
 3.ATTIC INSTALLATION OF THE AHU'S
 SHALL COMPLY WITH 2001 FBC CHAPTER 13
 SUB SECTION 610.1.ABC.3.5.2 AND 2001
 FBC(M) 306.3.
  
 4.SEE COMMENT #1 BY KEN STEVENS, DATE
 MISSING FROM SIGNATURE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.