Plan Review Notes For Permit 03091830 |
Permit Number |
03091830 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-11-17 00:00:00 | DENIED: | | 1.ENERGY CALCULATIONS SUBMITTED | | INDICATE 1 SYSTEM, 15 SEER.PLANS | | INDICATE TWO SYSTEMS AT 12.1 SEER. FORM | | 600C SUBMITTED FOR SYSTEM 1 AT 12.1 | | SEER. PLEASE CORRELATE ENERGY CALCS AND | | MANUAL J CALCS. | | | | 2.AUXILIARY DRAIN PANS REQUIRED AS PER | | 2001 FBC(M) 307.2.3. | | | | 3.ATTIC INSTALLATION OF THE AHU'S | | SHALL COMPLY WITH 2001 FBC CHAPTER 13 | | SUB SECTION 610.1.ABC.3.5.2 AND 2001 | | FBC(M) 306.3. | | | | 4.SEE COMMENT #1 BY KEN STEVENS, DATE | | MISSING FROM SIGNATURE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|