Plan Review Notes
Plan Review Notes For Permit 03091689
Permit Number 03091689
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-02 00:00:00************ UNSAT *************
  
 1)NOTE: PLEASE SEE FBC/ADMIN 104.2.1,
 PLEASE PROVIDE INFORMATION FOR PERSON
 RESPONSIBLE FOR PLANS.
  
 2)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 FOR BOTH PANELS A&B. PLEASE LIST AWG AND
 OCP FOR ALL CIRCUITS.PLEASE LIST ALL
 MIN CIRCUITS.215.5
 3)NOTE: PLEASE LIST THE REQ'D DEDICATED
 BATH(S) CIRCUIT(S) 210.52D/ 210.11C3
  
 4)NOTE: PLEASE LIST ALL ARC FAULT
 PROTECTED CIRCUITS. 210.12
 IT WAS NOTED ON PLAN.
  
 5)NOTE: PLEASE SEE THAT AS OF JULY 1ST,
 2003 WE ARE UNDE RTHE 2002 NEC.
  
 6)NOTE: PLEASE RELOCATE SD IN MASTER
 BEDROOM HALL INTO BEDROOM AREA.
 NFPA-72 8-1.4.2
  
 7)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 BEDROOM #2.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  