2003-10-21 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT A PAID RECEIPT FOR THE IMPACT |
| FEES. |
| |
| 3) SUBMIT A SUB-SURFACE SOIL REPORT |
| INDICATING THE SAFE BEARING CAPACITY OF |
| THE SOIL AS REQUIRED BY FBC 1804.2.2. |
| |
| 4) THE ENERGY CALCULATIONS ARE REQUIRED |
| TO BE SIGNED BY THE OWNER/AGENT. IN |
| ORDER TO TAKE THE CEILING FAN CREDIT ON |
| THE ENERGY CALCS, A MINIMUM OF ONE |
| CEILING FAN IS REQUIRED IN ALL PRIMARY |
| LIVING AREAS. THERE IS NO CEILNG FAN |
| SPECIFIED IN THE LIVING ROOM. PLEASE |
| INDICATE THE REQUIRED SIZES OF THE FANS |
| ON THE PLANS. SEE FBC 13-607.2.A.3.1 AND |
| TABLE 6-6. |
| |
| 5) SUBMIT A SIGNED AND SEALED SURVEY. |
| |
| 6) INDICATE ON THE PLANS THE SQFT |
| BREAKDOWN OF THE STRUCTURE. (A/C AREA, |
| GARAGE, COVERED PORCHES, ETC.) |
| |
| 7) THE GARAGE BUCK DETAIL 3B ON 4S4 |
| REQUIRES A MINIMUM OF 8X16 BLOCK WITH |
| TWO FILLED CELLS WITH ONE #5 ON EACH |
| SIDE OF THE GARAGE OPENINGS. THE PLAN |
| SPECIFIES ONE REINFORCED FILLED CELL ON |
| EACH SIDE OF THE OPENINGS. PLEASE |
| CORRECT. |
| |
| 8) THE FOUNDATION PLAN ON SHEET 4 |
| SPECIFIES WIRE MESH IN THE SLAB AND |
| DETAIL 1 ON 4S1 SPECIFIES FIBER MESH |
| CONCRETE FOR THE SLAB. PLEASE CLARIFY. |
| |
| 9) THE SECTION AT THE GARAGE DOOR ON 4 |
| IS MISLABELED. IT SHOULD BE LABELED 3 |
| ON 4S1. |
| |
| 10) DETAIL 8 ON 4S1 FOR THE SECTION AT |
| THE INTERIOR GARAGE WALL REFERENCED ON |
| SHEET 4 HAS BEEN CROSSED OUT. PLEASE |
| CORRECT. |
| |
| 11) PLEASE MAKE CORRECTIONS TO CONNECTOR |
| CHART ON 5B. THE 775# UPLIFT VALUE IS |
| FOR 10D NAILS. THE VALUE FOR 10D X 1-1/2 |
| NAILS 735#. THE USP TAPR216 CONNECTOR IS |
| NO LONGER LISTED IN THE CATALOG. SPECIFY |
| A CURRENT CONNECTOR. THE LONGER HTT 22 |
| STRAP WILL BE REQUIRED FOR THE (32) 10D |
| NAILS FOR A 5370# UPLIFT. THE UPLIFT FOR |
| THE NFM6X16 HAS BEEN REVISED TO 1325# IN |
| THE 2003 USP CATALOG. PLEASE REVISE. |
| SEE 2003 USP CATALOG. |
| |
| 12) PLEASE PROVIDE MANUFACTURER'S SPECS. |
| AND LISTING INFORMATION FOR GAS COOK TOP |
| ON COVERED PATIO. |
| |
| 13) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| INDICATING THE HORIZONTAL SLIDING |
| WINDOW IN BEDROOM #4 MEETS THE EGRESS |
| REQUIREMENTS OF FBC 1005.4. |
| |
| 14)FBC 1005.4.5 (GLITCH AMENDMENTS |
| JULY 1, 2003) REQUIRES AT LEAST ONE |
| MEANS OF ESCAPE FROM A DWELLING WHEN |
| SHUTTERED FOR IMPACT PROTECTION. THE |
| MEANS OF ESCAPE SHALL BE WITHIN THE |
| FIRST FLOOR OF THE DWELLING AND CAN NOT |
| BE LOCATED IN A GARAGE. OCCUPANTS IN ANY |
| PART OF THE DWELLING SHALL HAVE ACCESS |
| TO IT WITHOUT HAVING TO PASS THROUGH A |
| LOCKABLE DOOR NOT UNDER THEIR CONTROL. |
| INDICATE HOW COMPLIANCE WILL BE |
| ACHIEVED. |
| |
| 15) INDICATE THE LOCATION AND SIZE OF |
| THE ATTIC ACCESS REQUIRED BY FBC 2309.6. |
| |
| 16) SUBMIT THE ENGINEERED INSTALLATION |
| DRAWINGS FOR THE STORM PANELS. SUBMIT A |
| KEY PLAN THAT CORRESPONDS TO THE |
| INSTALLATION SCHEDULE. THE NUMBERS AND |
| SIZES ON THE SHUTTER SCHEDULE DOES NOT |
| CORRESPOND WITH THE SHUTTER SCHEDULE ON |
| 4S4. |
| |
| 17) SUBMIT SITE SPECIFIC ENGINEERING W/ |
| DETAILED SHOP DRAWINGS, SPECIFICATIONS |
| AND RATIONAL ANALYSIS AND/OR TEST DATA |
| ASSURING SAFE PERFORMANCE FOR THE BUTT |
| GLASS ASSEMBLY IN THE MORNING ROOM. THE |
| PRODUCT APPROVAL FOR THE STORE FRONT |
| THAT WAS SUBMITTED IS NOT FOR A BUTT |
| GLASS ASSEMBLY. |
| |
| 18) THE PRODUCT APPROVAL SUBMITTED FOR |
| THE HORIZONTAL SLIDING WINDOWS DOES NOT |
| LIST A THREE PANEL WINDOW AS SHOWN FOR |
| BEDROOM #4. SUBMIT APPROPRIATE PRODUCT |
| APPROVAL. |
| |
| 19) THE REQUIRED WINDLOAD PRESSURES FOR |
| THE 36SH WINDOWS IN THE MASTER BEDROOM |
| EXCEED THE NEGATIVE PRESSURE OF -43.10 |
| IN THE PRODUCT APPROVAL FOR 3/16" |
| ANNEALED GLASS. SUBMIT APPROPRIATE |
| PRODUCT APPROVAL. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |