Plan Review Notes For Permit 03091365 |
Permit Number |
03091365 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-02 00:00:00 | PROVISO: | | 1. PLEASE NOTE,REVISION TO THE 2001 | | FBC(M)601.4, EFFECTIVE JUNE 30, 2003: | | | | BALANCED AIR RETURN - RETURN/TRANSFER | | SHALL BE 1 1/2 TIME THE CROSS SECTIONAL | | AREA OF THE SUPPLY DUCT ENTERING THE | | ROOM ITS SERVING & THE DOOR HAVING AN | | UNRESTRICTED 1" UNDERCUT. | | | | ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. | | | | 2. OVERFLOW PROTECTION REQUIRED FOR AHU1 | | AS WELL AS SHU2 PER 2001 FBC(M) | | 307.2.3 & 307.2.4. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|