Plan Review Notes
Plan Review Notes For Permit 03091361
Permit Number 03091361
Review Stop M
Sequence Number 1
Notes
Date Text
2003-10-02 00:00:00PROVISO:
 1. PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 2. OVERFLOW PROTECTION REQUIRED FOR AHU1
 AS WELL AS AHU2 PER 2001 FBC(M)
 307.2.3 & 307.2.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.