Plan Review Notes
Plan Review Notes For Permit 03091348
Permit Number 03091348
Review Stop E
Sequence Number 5
Notes
Date Text
2004-05-08 00:00:00**** REDLINED *****
  
 1)NOTE: NEUTRAL CONDUCTOR FROM METER TO
 277/480V PANEL SHOWN AS #4 WHICH IS
 RATED FOR 85'S PER 310.16 75 DEGREE
 COL.
 PLEASE SEE NEUTRAL LOAD EXCEEDS RATING
 OF AWG. LOAD SHOWN AT 92.5A'S.
  
 PLANS NOTED.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW