2004-05-05 00:00:00 | ************* UNSAT *************** |
| |
| PLEASE SEE RISER DIAGRAM NOW SUBMITTED |
| HAS COMPLETELY CHANGED FROM ORIG SET. |
| |
| PLEASE SEE ATTACH INSPECTIONS. |
| |
| 1)NOTE: PLEASE SEE 250.6,250.24, NO |
| EQUIPMENT GROUNDING CONDUCTORS ARE TO |
| BE INSTALLED BETWEEN METEE AND THE FIRST |
| MEANS OF DISC. |
| |
| 2)NOTE: RISER IS NOW SHOWING LINE AND |
| LOAD BEING INSTALLED IN THE METER???? |
| |
| 3)NOTE: PLEASE SEE PLANS ARE NOW SHOWING |
| A 54KW WATER HEATER. WHERE IS THIS WH |
| BEING FED FROM. THERE IS A WH SHOWN |
| ON 100A 120/240 SINGLE PHASE PANEL, YET |
| OCP IS SHOWN AS 20A1-POLE? |
| THIS WATER HEATER IS RATED FOR 225A'S |
| ON A 100A PANEL?? |
| PLEASE ALSO SEE 422.1,422.13 ETC FOR OCP |
| |
| 4)NOTE: PLEASE BE SURE TO SHOW ALL |
| EQUIPMENT AND CIRCUITING ON PLANS AND |
| CORRELATE WITH THE SUBMITTED PANEL |
| SCHEDULES. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |