Plan Review Notes For Permit 03091348 |
Permit Number |
03091348 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-11-04 00:00:00 | ************* UNSAT ****************** | | | | 1)NOTE: PLEASE SEE THAT MOST NOTES FROM | | FIRST REVIEW STILL NEED TO BE ADDRESSED. | | PLEASE CORRELATE RISER/PANEL SCHEDULES | | ETC. | | PLEASE SEE ORIG NOTES. | | | | 2)NOTE: PLEASE SEE NOW ONLY SHEET E-2 | | IS SIGNED AND SEALED BY A PE. PLEASE | | SEE FS AND FAC AND FBC, ALL E-SHEETS | | MUST BE SIGNED,DATED AND SEALED BY PE. | | 471.003,61G15-23.002, 104.4.1.3 | | | | 3)NOTE: PLEASE ALSO SEE THAT COMPLETE | | TITLE BLOCKS ARE REQ'F OR ENGINEER OF | | RECORD PER FAC 61G15-23.002, AND ALL | | INFORMATION AS SET FORTH. | | | | 4)NOTE; PLEASE SEE ATTACHED COPY OF | | FS 553.80(2)(B) FOR PLANS REVIEW WITH | | THE SAME COMMENTS.THIS IS BEING NOTED | | AFTER SECOND REVIEW AND NEEDS TO HAVE | | ALL COMMENTS ADDRESSED. | | | | PLEASE REMOVE ALL OLD/ VOIDED SHEETS AND | | INSERT NEW SHEETS INTO TWO COMPLETE SETS | | FOR REVIEW AND STAMPING. | | PLEASE SEE COMMENTS FROM OTHERE REVIEWER | | -S THAT MAY HAVE AN AFECT ON ELECTRICAL | | PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|