Plan Review Notes
Plan Review Notes For Permit 03091348
Permit Number 03091348
Review Stop E
Sequence Number 1
Notes
Date Text
2003-10-06 00:00:00************** UNSAT *******************
  
 1)NOTE: PLANS REQ'D TO BE SIGNED, DATED
 AND SEALED BY AN ENGINEER. PER FS 471
 AND FAC 553.79(6)(A) FOR 277/480V
 SYSTEMS.
  
 2)NOTE: PLEASE SHOW COMPLETE CONNECTIONS
 FOR GROUNDING ELECTRODE SYSTEM AND TRANS
 -FORMER. 250.50 AND 250.30
  
 3)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 CONDUCTORS FOR X-FORMER FEED WITH RISER
 DIAGRAM. ONE SHOWS # 6'S AND OTHER SHOWS
 #8.
  
 4)NOTE: PLEASE SPECIFY WHAT MATERIALS
 AND/OR ANY CLASS LOCATIONS FOR STORAGE
 AREA. PLEASE SEE 384.7/ 110.26 ALSO.
 AREA ABOUT ELECTRICAL EQUIPMENT SHOULD
 ALSO HAVE FLR AREA STRIPED FOR REQ'D
 CLEARENCES TO REMAIN.
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]