2003-10-09 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) FBC 1027.1STORAGE ROOM EXIT.A |
| MINIMUM OF TWO EXITS FROM THE STORAGE |
| ROOM ARE REQUIRED (REF ALSO: 1004.1.2). |
| AT LEAST TWO OF THE EXITS SHALL BE |
| SEPARATED BY A DISTANCE EQUAL TO NOT |
| LESS THAN 1/2 THE DIAGONAL DIMENSION OF |
| THE ROOM (REF: 1004.1.4). |
| |
| 2) FBC 301.3STORAGE.ANNOTATE THE |
| PLANS TO SPECIFY THE MATERIALS THAT ARE |
| TO BE STORED.SEE FBC 308 FOR MATERIALS |
| AND QUANTITIES THAT ARE CLASSIFIED AS |
| HAZARDOUS OCCUPANCY. |
| |
| 3) AMEND SHEET SP-1 AS FOLLOWS: |
| (A) GENERAL NOTE #3 REFERS TO "....2001 |
| FLORIDA BUILDING CODE, WITH 2002 |
| AMENDMENTS."THE REFERENCE SHALL ALSO |
| INCLUDE THE 2003 AMENDMENTS (EFFECTIVE |
| JUNE 30, 2003). |
| (B) THE ABOVE COMMENT ALSO APPLIES TO |
| THE BUILDING CODE ANALYSIS TABLE.AMEND |
| THE TABLE. |
| (C) THE BUILDING CODE ANALYSIS TABLE |
| STATES "FIRE DISTRICT:N/A".THE |
| BUILDING WILL BE IN THE FIRE DISTRICT. |
| AMEND THE TABLE. |
| |
| 4) FBC* F102.2.4FIRE DISTRICT. |
| ROOF COVERING IN THE FIRE DISTRICT SHALL |
| CONFORM TO THE REQUIREMENTS OF CLASS A |
| OR CLASS B ROOF COVERINGS AS DEFINED IN |
| 1505.ANNOTATE THE PLANS TO STATE THE |
| REQUIRED FIRE CLASSIFICATION FOR THE |
| ROOF COVERING. |
| |
| 5) FBC 1804.1.3 DETAIL 2/S-3. THE BOTTOM |
| OF FOUNDATIONS SHALL EXTEND NO LESS THAN |
| 12 INCHES (305 MM) BELOW FINISH GRADE. |
| ANNOTATE THE PLANS TO SHOW THE REQUIRED |
| MINIMUM DEPTH. |
| |
| 6) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 7) SUBMIT TWO COPIES OF A PRODUCT |
| APPROVAL FOR THE PROPOSED BUILT UP |
| ROOFING SYSTEM, OR A SEPARATE ROOFING |
| PERMIT, AND FEES, WILL BE REQUIRED. |
| THE PRODUCT APPROVAL SHEETS SHALL BE |
| MARKED, AS APPROPRIATE TO IDENTIFY WHICH |
| PRODUCT OPTIONS/MATERIALS ARE TO BE USED |
| |
| 8) SUBMIT TWO COPIES OF A PRODUCT |
| APPROVAL FOR THE PERSONNEL DOORS AND THE |
| SECTIONAL DOORS. |
| THE PRODUCT APPROVAL SHEETS SHALL BE |
| MARKED, AS APPROPRIATE TO IDENTIFY WHICH |
| PRODUCT OPTIONS/MATERIALS/SIZES ARE TO |
| BE USED. |
| |
| 9) IF NEW PLAN SHEETS ARE REQUIRED, IN |
| ORDER TO ADDRESS THE ABOVE COMMENTS, THE |
| OLD SHEETS SHALL BE REMOVED AND THE NEW |
| SHEETS INSERTED.ONE COPY OF EACH OLD |
| SHEET SHALL BE INCLUDED WITH THE |
| RESUBMITTAL FOR COMPARISON OF REVISIONS. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |