Plan Review Notes For Permit 03091208 |
Permit Number |
03091208 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2004-01-12 00:00:00 | ************UNSAT ***************** | | | | PLEASE SEE NEW SHEET E400 IS NOW SHOWING | | TRANSFORMER GROUNDING DETAIL, HOWEVER | | NO GROUNDING/BONDING CONDUCTOR SIZES | | ARE SHOWN? | | PLEASE SEE 250.30, A-D | | | | PLEASE ADJUST E-400. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|