2003-12-02 00:00:00 | ************ PROVISO/ NOTES ******* | | | | 1)NOTE: PLEASE SEE THAT SHEET E-400 HAS | | NOT BEEN CHANGED OUT TO INCLUDE NEW | | REVISED SHEET WITH TRASNFORMER GROUNDING | | DETAIL. | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS | | FOR NEW PANELS AND ALL CONTINUOUAS LOADS | | AT 125%. LOADS ARE NOW SHOWN AS CONNECT- | | ED LOADS W/OUT SHOWING CONTINUOUS LOAD | | FACTOR. 215.3,230.42 ETC | | | | 3)NOTE: IT HAS BEEN NOTED FOR CONTRACTOR | | TO PROVIDE LOAD CALCULATIONS AND REVISED | | PANEL SCHEDULES AT COMPLETION OF WORK | | IN ORDER TO VERIFY WEATHER OR NOT PANELS | | ARE OVERLOADED. PLEASE BE INFORMED: | | THIS WILL NOT BE PERMITTED AND COMPLETE | | LOAD CALCULATIONS AND CORRELATING PANEL | | SCHEDULES WITH CORRELATING CIRCUIT #`S | | WILL BE REQ'D BEFORE ROUGH ELECTRICAL | | INSPECTION IS CALLED IN. THESE MUST BE | | SUBMITTED FOR REVIEW. | | NEC 215.5, 215.3, 220. | | DUE TO THE MANY ITEMS BEING ADDED TO | | BLDG OVER THE YEARS AND THE AGE OF | | EXISTING PANELS. THERE IS SOME CONCERN | | OVER EXISTING LOADS ON PANELS. | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. IF | | THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|