2003-11-25 00:00:00 | |
| UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| 1} THE REFERENCES TO A GENERATOR BACKED |
| SYSTEM ON E-001 ARE NOT SHOWN ON THE |
| RISER DIAGRAM. THE PLAN ALSO SHOWS BOTH |
| HIGH AND LOW VOLTAGE LIGHTS ON THE |
| EMERGENCY SYSTEM.PLEASE PROVIDE DETAILS |
| OF THOSE SYSTEMS.(EMERGENCY). |
| |
| 2} RESPONSE 1C REGARDING THE CONTRACTOR |
| TO TAKE LOAD READINGS "AT THE COMPLETION |
| OF WORK TO ENSURE THAT PANELS ARE NOT |
| OVERLOADED" IS UNACCEPTABLE. THE DESIGN |
| PROFESSIONAL SHALL DETERMINE THAT |
| PANELS ARE NOT OVERLOADED PRIOR TO |
| BEGINNING WORK. |
| |
| 3} PLEASE SEE NOTE #2 FROM LAST REVIEW. |
| VERIFY CIRCUIT NUMBERS IN THE PANELS AND |
| ON PLAN. LABEL THE CIRCUITS SO THAT |
| LOADS CAN BE CORRECTLY CALCULATED. |
| |
| 4} THE "ESTIMATED LOADS" ON THE |
| CALCULATIONS DO NOT REFLECT CONTINUOUS |
| AND NONCONTINUOUS LOADS PER |
| 210.19,215.2,215.3, 220.3 OR |
| 220.3(B)(4).REFER TO WATTAGES OF |
| RECESSED LUMINAIRES ON SHEET E-002. |
| |
| 5} PLEASE SUPPLY A CONTROL DETAIL |
| SHOWING HOW THE "RELAY" FOR THE |
| EMERGENCY LIGHTING WILL WORK IN |
| CONJUNTION WITH SWITCHES AND DIMMERS |
| SHOWN CONTROLLING EMERGENCY FIXTURES ON |
| SHEET E-150. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |