2003-11-25 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 1} THE REFERENCES TO A GENERATOR BACKED
 SYSTEM ON E-001 ARE NOT SHOWN ON THE
 RISER DIAGRAM. THE PLAN ALSO SHOWS BOTH
 HIGH AND LOW VOLTAGE LIGHTS ON THE
 EMERGENCY SYSTEM.PLEASE PROVIDE DETAILS
 OF THOSE SYSTEMS.(EMERGENCY).
  
 2} RESPONSE 1C REGARDING THE CONTRACTOR
 TO TAKE LOAD READINGS "AT THE COMPLETION
 OF WORK TO ENSURE THAT PANELS ARE NOT
 OVERLOADED" IS UNACCEPTABLE. THE DESIGN
 PROFESSIONAL SHALL DETERMINE THAT
 PANELS ARE NOT OVERLOADED PRIOR TO
 BEGINNING WORK.
  
 3} PLEASE SEE NOTE #2 FROM LAST REVIEW.
 VERIFY CIRCUIT NUMBERS IN THE PANELS AND
 ON PLAN. LABEL THE CIRCUITS SO THAT
 LOADS CAN BE CORRECTLY CALCULATED.
  
 4} THE "ESTIMATED LOADS" ON THE
 CALCULATIONS DO NOT REFLECT CONTINUOUS
 AND NONCONTINUOUS LOADS PER
 210.19,215.2,215.3, 220.3 OR
 220.3(B)(4).REFER TO WATTAGES OF
 RECESSED LUMINAIRES ON SHEET E-002.
  
 5} PLEASE SUPPLY A CONTROL DETAIL
 SHOWING HOW THE "RELAY" FOR THE
 EMERGENCY LIGHTING WILL WORK IN
 CONJUNTION WITH SWITCHES AND DIMMERS
 SHOWN CONTROLLING EMERGENCY FIXTURES ON
 SHEET E-150.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW