Plan Review Notes For Permit 03091208 |
Permit Number |
03091208 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-27 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | | | 1) RESPONSE TO COMENT #1 FROM PREVIOUS | | REVIEW NOTED: INSPECTION FOR CAPPED | | PLUMBING LINES REQUIRED TO VERIFY THAT | | LINES ARE CAPPED PER CODE. SEE SHEETS | | MP-60 & MP-61. | | 2) DATE NOT ON SEAL AS REQUIRED BY SEC. | | 61G15-23.002(1) SEE ATTACHED SHEET FOR | | REFERENCE. | | 3) SHT MP-201 DETAIL 2/MP-201 MEN'S AND | | WOMEN'S POOL TOILETS 1ST FLOOR NEW - TO | | BE ROUTED TO THE PALM BEACH CTNY HEALTH | | UNIT DIVISION OF ENVIRONMENTAL HEALTH | | 901 EVERNIA STREET FOR REVIEW & APPROVAL | | 4) HOSPITALITY ROOM, EXERCISE ROOM AND | | CONFERENCE ROOM TO BE ACCESSIBLE. SHT | | MP-201. PROVIDE DETAILS. | | 5) SHT MP-301 ALL WATER RISER DIAGRAMS, | | ALL WATER HAMMER ARRESTORS SHALL BE | | LOCATED NEAR THE FIXTURES IN AN "EFFECT- | | IVE RANGE" NOT IN THE CEILING AS SHOWN. | | PDI-WH 201 AND MANUF. INSTALL. INSTRUCT. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|