Plan Review Notes
Plan Review Notes For Permit 03091208
Permit Number 03091208
Review Stop P
Sequence Number 1
Notes
Date Text
2003-10-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) RESPONSE TO COMENT #1 FROM PREVIOUS
 REVIEW NOTED: INSPECTION FOR CAPPED
 PLUMBING LINES REQUIRED TO VERIFY THAT
 LINES ARE CAPPED PER CODE. SEE SHEETS
 MP-60 & MP-61.
 2) DATE NOT ON SEAL AS REQUIRED BY SEC.
 61G15-23.002(1) SEE ATTACHED SHEET FOR
 REFERENCE.
 3) SHT MP-201 DETAIL 2/MP-201 MEN'S AND
 WOMEN'S POOL TOILETS 1ST FLOOR NEW - TO
 BE ROUTED TO THE PALM BEACH CTNY HEALTH
 UNIT DIVISION OF ENVIRONMENTAL HEALTH
 901 EVERNIA STREET FOR REVIEW & APPROVAL
 4) HOSPITALITY ROOM, EXERCISE ROOM AND
 CONFERENCE ROOM TO BE ACCESSIBLE. SHT
 MP-201. PROVIDE DETAILS.
 5) SHT MP-301 ALL WATER RISER DIAGRAMS,
 ALL WATER HAMMER ARRESTORS SHALL BE
 LOCATED NEAR THE FIXTURES IN AN "EFFECT-
 IVE RANGE" NOT IN THE CEILING AS SHOWN.
 PDI-WH 201 AND MANUF. INSTALL. INSTRUCT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]