Plan Review Notes For Permit 03091207 |
Permit Number |
03091207 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2003-12-16 00:00:00 | **************** UNSAT ************** | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS | | LOADS AT 125%. 215.3,230.42 ETC. | | | | 2)NOTE: PLEASE PROVIDE PHOTOMETRIC | | STUDY/DIAGRAM AND PLEASE HAVE REVIEWED | | AND STAMPED BY PALM BEACH COUNTY HEALTH | | DEPT. THIS IS REQ'D FOR ANY AND ALL | | SWIMMING AFTER DUSK. | | | | 3)NOTE: PLEASE PROVIDE LATEST REVISED | | RISER DIAGRAM. | | E-300 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|