2003-10-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03091207 PHASE 1-A
 10TH & 9TH FLOORS
 ADD: 630 CLEARWATER PARK RD
  
 CONT: THE WHITING-TURNER CONT CO
 TEL: (954)776-0800
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED.
 MISSING ALL PRODUCT APPROVALS!!!!!!!!!!
  
 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
  
 GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 2)EFIS SYSTEM EXTERIOR WALL COVERINGS:
 ARE TO COMPLY WITH 2603.6 (1-7)
 (1) PROVIDE TESTING IN ACCORDANCE WITH
 ASTM E 119
 (2) THERMAL BARRIER
 (3) POTENIAL HEAT
 (4) FLAME SPREAD/ SMOKE DEVELOPMENT
 (5) TEST STANDARD
 (6) LABEL REQUIRED
 (7) IGNITION
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026