2005-03-07 00:00:00 | *** UNSAT *** | | | | 1)NOTE: PLEASE SEE PREVIOUS NOTES FOR | | LOAD CALCULATIONS. | | | | PLEASE SEE MIN .25 PER SQ FT: | | ACTUAL LIGHTING 600W PER FIXTURE: | | BOTH AT 125%= TOTAL LIGHTING LOAD PLUS | | OTHER LOADS. | | 180VA PER RECEPT: | | | | | | PLEASER SUBMIT THE ABOVE AND IF THERE | | ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|