Plan Review Notes
Plan Review Notes For Permit 03091152
Permit Number 03091152
Review Stop E
Sequence Number 4
Notes
Date Text
2005-02-02 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SEE EM LTS ARE NOTED AS
 BEING ON LOCAL BRANCH CIRCUIT(S),
 HOWEVER PANEL SCHEDULE INDICATES EMLT ON
 SEPARATE CIRCUIT.\
 PLEASE CORRELATE.
 700.12E,215.5
  
 2)NOTE: PLEASE 220 FOR LOAD
 CALCULATIONS
 ARE TO BE DONE PER
 220.3,220.10,220.11,220.13,PLEASE ALSO
 SEE 220.3B5 FOR NEW HIGH BAY FIXTURES
 SHOWN.
  
  
 PLEASE CLARIFY, ORIG LOADS HAVE NOW BEEN
 DECREASES BY HALF , YET SERVICE SIZE HAS
 DOUBLED?
 PLEASE SEE 215.3, 230.42 ETC FOR ALL
 CONTINUOUS(LIGHTING ETC) TO BE SHOWN AT
 125%.
  
 3)NOTE: PLEASE SEE SEC'S ARE NOW SHOWN,
 YET PLEASE SEE MIN SIZE FOR MAIN BRKRS.
 PER 310.16, 240.4
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]