Plan Review Notes
Plan Review Notes For Permit 03091152
Permit Number 03091152
Review Stop P
Sequence Number 2
Notes
Date Text
2003-12-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING.
  
 1) GUTTERS WITH DOWNSPOUTS ARE REQUIRED
 ON ALL BUILDINGS WITH EVES OF LESS THAN
 6" HORIZONTAL PROJECTION EXCEPT FOR GAB-
 LE END RAKES OR ON A ROOF ABOVE ANOTHER
 ROOF. SECTION 1503.4.4 - ROOF DOWNSPOUTS
 SHALL DISCHARGE AT LEAST 1' AWAY FROM
 THE STRUCTURE SIDEWALL. 1503.4.4
 2) FROM PREVIOUS REVIEW: SUBMIT CALCUL-
 ATIONS FOR ROOF GUTTERS AND DOWNSPOUTS
 PER TABLE 1106.6. SHOW SQ. FT. AREA FOR
 EACH SECTION AND SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO SQ. FT. OF ROOF SECTIONS. INDICATE
 SIZE OF GUTTERS AND DOWNSPOUTS. SHOW
 LOCATION OF DOWNSPOUTS, HIGH SPOTS OF
 GUTTER AND DIRECTION OF SLOPE OF GUTTERS
 ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]