Plan Review Notes For Permit 03091152 |
Permit Number |
03091152 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-12-15 00:00:00 | **************** UNSAT ************* | | | | PLEASE SEE NOTES FROM FIRST REVIEW. | | PLEASE SEE THAT SOME NOTES STILL NEED | | TO BE ADDRESSED. | | NOTES: 2,4,6, | | | | 1)NOTE: PLEASE PROVIDE TECHNICAL INFOR- | | -MATION ON PANELS/SCHEDULES. DEATILS | | ON PANELS ARE SHOWN BLANK IN THE UPPER | | LEFT HAND CORNER. | | | | 2)NOTE: PLEAS CLARIFY GROUNDING ELEC- | | -TRODE CONDUCTOR,: SHOWS A 2/0 WHICH IS | | OK PER 250.66, BUT ALSO SHOWS A #4 BARE? | | PLEASE CORRECT. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | | | PLEASE SEE COPY OF FS 553.80(2)(B) | | ATTACHED. PLEASE ADDRESS ALL COMMENTS. |
|