2003-09-19 00:00:00************* UNSAT *****************
  
 1)NOTE: PLANS NEED TO BE SIGNED, DATED
 AND SEALED BY THE ARCH OF RECORD.
 PER FAC 61G1-16.004 AND FS 481.221
  
 2)NOTE: PLEASE SEE MISSING RECEPTS
 PER 210.52, 210.52H, 210.63,210.52C1
 PLEASE SEE THAT ONE SET HAS HIGHLIGHTED
 AREAS.
  
 3)NOTE: PLEASE PROVIDE A COMPLETE PANEL
 SCHEDULE FOR MIN CIRCUITS REQ'D PER NEC.
 PLEASE NOTE, WE ARE NOW UNDER THE 2002
 NEC.
  
 4)NOTE: PLEASE INDICATE SIZE OF EXISTING
 OR NEW SERVICE?
 LOCATION OF SERV AND/OR PANEL.
 PLEASE SEE THAT IT APPEARS HOUSE EXCEEDS
 50% OF REWROK UNDER CHAPTER 34 OF THE
 FBC, THEREFORE ALL ELECTRICAL WILL BE
 REQ'D TO BE BROUGHT UP TO CURRENT CODE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  