Plan Review Notes For Permit 03090989 |
Permit Number |
03090989 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-19 00:00:00 | ************* UNSAT ***************** | | | | 1)NOTE: PLANS NEED TO BE SIGNED, DATED | | AND SEALED BY THE ARCH OF RECORD. | | PER FAC 61G1-16.004 AND FS 481.221 | | | | 2)NOTE: PLEASE SEE MISSING RECEPTS | | PER 210.52, 210.52H, 210.63,210.52C1 | | PLEASE SEE THAT ONE SET HAS HIGHLIGHTED | | AREAS. | | | | 3)NOTE: PLEASE PROVIDE A COMPLETE PANEL | | SCHEDULE FOR MIN CIRCUITS REQ'D PER NEC. | | PLEASE NOTE, WE ARE NOW UNDER THE 2002 | | NEC. | | | | 4)NOTE: PLEASE INDICATE SIZE OF EXISTING | | OR NEW SERVICE? | | LOCATION OF SERV AND/OR PANEL. | | PLEASE SEE THAT IT APPEARS HOUSE EXCEEDS | | 50% OF REWROK UNDER CHAPTER 34 OF THE | | FBC, THEREFORE ALL ELECTRICAL WILL BE | | REQ'D TO BE BROUGHT UP TO CURRENT CODE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|