Plan Review Notes
Plan Review Notes For Permit 03090979
Permit Number 03090979
Review Stop B
Sequence Number 3
Notes
Date Text
2004-08-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 THIRD REVIEW, ARCHITECTURAL PLANS DATED
 12/22/03, STRUCTURAL PLANS DATED
 12/19/03.
  
 1.)SEE PREVIOUS TWO LISTS.PROVIDE A
 SURVEY.THE SITE PLAN, SHEET 2.1 STILL
 DOES NOT HAVE ANY HORIZONTAL CONTROL
 DIMENSIONS TO LOCATE THE BUILDING.
 PROPERTY LINES ARE NOT IDENTIFIED.SEE
 ATTACHED IN REGARDS TO FS553.80(2)(B).
 CODE COMPLIANCE FOR TABLE 600 CANNOT
 BE DETERMINED WITHOUT A DIMENSIONED
 SITE PLAN.DESIGNER OF RECORD IS
 RESPONSIBLE TO SUBMIT ALL PLANS IN
 COMPLIANCE WITH FBC104.3.1.1.SEE
 SECTION (1), SITE REQUIREMENTS.
  
 2.)THE SHEETS PREPARED BY WE SCHIPSKE
 PE CONTAIN A PHOTOCOPY OF A SIGNATURE.
 THIS MUST BE AN ORIGINAL SIGNATURE
 FAC61G15-23.002.THE EMBOSSED SEAL IS
 TO BE LEGIBLE.
  
 3.)THE FP SHEETS AND CALCS LACK A
 TITLE BLOCK REQUIRED BY FAC61G15-23.002.
  
 4.)6-S3, STUCCO IN A VERTICAL
 APPLICATION OVER WIRE LATH IS TO BE
 7/8" MIN, FBC2405.2.2, ASTM C926.CHECK
 ALL DETAILS (WILL REDLINE).
  
 5.)SEE PREVIOUS LIST, CORRECTIONS
 6 THROUGH 10.NOT ADDRESSED.FOR YOUR
 CONVENIENCE, THEY ARE:
  
 PLEASE PROVIDE THE SPECIFICATION FOR THE
 HIGH LIFT GROUTING CALLED OUT IN NOTE
 J(3) ON S3.
  
 COLUMNS SHOWN AS MC1 ARE NOT ON THE
 COLUMN SCHEDULE ON SHEET S3.
  
 THE REQUESTED COLUMN CONNECTINS FOR THE
 TS COLUMNS SHOWN ON SHEETS S1 AND S2
 HAVE NOT BEEN PROVIDED.
  
 SHEET S3 ROOF WIND ZONE SKETCH.DID
 THE ENGINEER USE THE SIMPLIFIED METHOD
 IN ASCE7-98 SUBSECTION 6.4 OR THE
 ANALYTICAL METHOD IN SECTION 6.5?IN
 EITHER CASE, HOW WERE THE EDGE AREAS OF
 4' AND 5' DETERMINED FOR A BUILDING WITH
 A LEAST DIMENSION OF 73' AND A MEAN
 ROOF HEIGHT OF 16.5'?
  
 SEE FBC 13-400.3 FOR COMPUTER BASED
 ENERGY CALCULATIONS AND THE ATTENDANT
 METHODS TO BE USED.ALSO, THE 6020 SF
 GROSS AREA INPUT DOES NOT AGREE WITH THE
 PLANS' 6700+ SQUARE FEET CONDITIONED
 AREA.PLEASE REVISE AS NECESSARY.
  
 THE IMPACT FEES AND NOAS CALLED OUT
 IN THE FIRST CHECKLIST REMAIN
 APPLICABLE.
  
 6.)BEFORE RESUBMITTING, PLEASE
 CONFIRM THAT THE COMPONENTS AND CLADDING
 PRODUCT APPROVALS SUBMITTED COMPLY WITH
 THE DESIGN CRITERIA ON SHEET 4.1.
 SHINGLES
 STEEL DOORS, DOUBLE AND SINGLE
 OVERHEAD DOOR
 LOUVERS
 IMPACT PROTECTION
 WINDOWS
  
 7.)I SEE FROM THE RESPONSE LETTER
 DATED 12/22/03, ITEM #12, IT INDICATES
 THAT THE DETAIL 11/10.3 DOES NOT EXIST.
 WHY DOES IT STILL APPEAR ON THE BUILDING
 PLANS?THERE IS STILL NO DETAIL FOR
 THE COLUMN.EXPLAINING IN A LETTER
 THE DESIGN INTENTION FOR THAT COLUMN
 DOES NOT PUT THAT ON THE BUILDING PLANS.
 PLEASE REMOVE THE REFERENCE TO THE
 MISSING 11-10.3 ON THE FOUNDATION PLAN
 AND INCLUDE THE METHOD OF ATTACHMENT
 FOR W10X22 TO THE MC1.
  
 8.)A RESPONSE WAS MADE THAT EACH
 MC1 ON REVISED S1 IS NOW MC4.THE PLANS
 STILL SHOW MC1.EITHER PROVIDE A
 SPECIFICATION FOR MC1 ON THE COLUMN
 SCHEDULE OR CHANGE THE MC1S ON THE PLAN
 TO MC4.
  
 9.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 10.) FOR MORE INFORMATION REGARDING
 THE IMPACT FEES REQUIRED, CALL 233-5025.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved