Date |
Text |
2004-08-04 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| THIRD REVIEW, ARCHITECTURAL PLANS DATED |
| 12/22/03, STRUCTURAL PLANS DATED |
| 12/19/03. |
| |
| 1.)SEE PREVIOUS TWO LISTS.PROVIDE A |
| SURVEY.THE SITE PLAN, SHEET 2.1 STILL |
| DOES NOT HAVE ANY HORIZONTAL CONTROL |
| DIMENSIONS TO LOCATE THE BUILDING. |
| PROPERTY LINES ARE NOT IDENTIFIED.SEE |
| ATTACHED IN REGARDS TO FS553.80(2)(B). |
| CODE COMPLIANCE FOR TABLE 600 CANNOT |
| BE DETERMINED WITHOUT A DIMENSIONED |
| SITE PLAN.DESIGNER OF RECORD IS |
| RESPONSIBLE TO SUBMIT ALL PLANS IN |
| COMPLIANCE WITH FBC104.3.1.1.SEE |
| SECTION (1), SITE REQUIREMENTS. |
| |
| 2.)THE SHEETS PREPARED BY WE SCHIPSKE |
| PE CONTAIN A PHOTOCOPY OF A SIGNATURE. |
| THIS MUST BE AN ORIGINAL SIGNATURE |
| FAC61G15-23.002.THE EMBOSSED SEAL IS |
| TO BE LEGIBLE. |
| |
| 3.)THE FP SHEETS AND CALCS LACK A |
| TITLE BLOCK REQUIRED BY FAC61G15-23.002. |
| |
| 4.)6-S3, STUCCO IN A VERTICAL |
| APPLICATION OVER WIRE LATH IS TO BE |
| 7/8" MIN, FBC2405.2.2, ASTM C926.CHECK |
| ALL DETAILS (WILL REDLINE). |
| |
| 5.)SEE PREVIOUS LIST, CORRECTIONS |
| 6 THROUGH 10.NOT ADDRESSED.FOR YOUR |
| CONVENIENCE, THEY ARE: |
| |
| PLEASE PROVIDE THE SPECIFICATION FOR THE |
| HIGH LIFT GROUTING CALLED OUT IN NOTE |
| J(3) ON S3. |
| |
| COLUMNS SHOWN AS MC1 ARE NOT ON THE |
| COLUMN SCHEDULE ON SHEET S3. |
| |
| THE REQUESTED COLUMN CONNECTINS FOR THE |
| TS COLUMNS SHOWN ON SHEETS S1 AND S2 |
| HAVE NOT BEEN PROVIDED. |
| |
| SHEET S3 ROOF WIND ZONE SKETCH.DID |
| THE ENGINEER USE THE SIMPLIFIED METHOD |
| IN ASCE7-98 SUBSECTION 6.4 OR THE |
| ANALYTICAL METHOD IN SECTION 6.5?IN |
| EITHER CASE, HOW WERE THE EDGE AREAS OF |
| 4' AND 5' DETERMINED FOR A BUILDING WITH |
| A LEAST DIMENSION OF 73' AND A MEAN |
| ROOF HEIGHT OF 16.5'? |
| |
| SEE FBC 13-400.3 FOR COMPUTER BASED |
| ENERGY CALCULATIONS AND THE ATTENDANT |
| METHODS TO BE USED.ALSO, THE 6020 SF |
| GROSS AREA INPUT DOES NOT AGREE WITH THE |
| PLANS' 6700+ SQUARE FEET CONDITIONED |
| AREA.PLEASE REVISE AS NECESSARY. |
| |
| THE IMPACT FEES AND NOAS CALLED OUT |
| IN THE FIRST CHECKLIST REMAIN |
| APPLICABLE. |
| |
| 6.)BEFORE RESUBMITTING, PLEASE |
| CONFIRM THAT THE COMPONENTS AND CLADDING |
| PRODUCT APPROVALS SUBMITTED COMPLY WITH |
| THE DESIGN CRITERIA ON SHEET 4.1. |
| SHINGLES |
| STEEL DOORS, DOUBLE AND SINGLE |
| OVERHEAD DOOR |
| LOUVERS |
| IMPACT PROTECTION |
| WINDOWS |
| |
| 7.)I SEE FROM THE RESPONSE LETTER |
| DATED 12/22/03, ITEM #12, IT INDICATES |
| THAT THE DETAIL 11/10.3 DOES NOT EXIST. |
| WHY DOES IT STILL APPEAR ON THE BUILDING |
| PLANS?THERE IS STILL NO DETAIL FOR |
| THE COLUMN.EXPLAINING IN A LETTER |
| THE DESIGN INTENTION FOR THAT COLUMN |
| DOES NOT PUT THAT ON THE BUILDING PLANS. |
| PLEASE REMOVE THE REFERENCE TO THE |
| MISSING 11-10.3 ON THE FOUNDATION PLAN |
| AND INCLUDE THE METHOD OF ATTACHMENT |
| FOR W10X22 TO THE MC1. |
| |
| 8.)A RESPONSE WAS MADE THAT EACH |
| MC1 ON REVISED S1 IS NOW MC4.THE PLANS |
| STILL SHOW MC1.EITHER PROVIDE A |
| SPECIFICATION FOR MC1 ON THE COLUMN |
| SCHEDULE OR CHANGE THE MC1S ON THE PLAN |
| TO MC4. |
| |
| 9.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 10.) FOR MORE INFORMATION REGARDING |
| THE IMPACT FEES REQUIRED, CALL 233-5025. |