2004-01-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
  
 1) PER CALCULATIONS PROVIDED IN RESPONSE
 TO 1ST REVIEW, MORE FIXTURES WILL BE RE-
 QUIRED PER TABLE 403. WITH THE CHURCH
 OCCUPANCY BEING 2958 DEVIDED BY 7 NET =
 422.57 ROUNDED UP TO 423 DIVIDED BY 2 =
 111.5 ROUNDED UP TO 112. PER POTTY PARI-
 TY THAT IS 2 FOR MEN & 3 FOR WOMEN. THE
 BUSINESS AREA IS 2824 DIVIDED BY 100 =
 28.24 ROUNDED UP TO 29 IS ONE WATER
 CLOSET AND STORAGE IS 965 DIVIDED BY
 300 (TABLE 1003.1) = 3.21 ROUNDED UP TO
 4. ADDED TO THE 29 FROM BUSINESS THERE
 WILL STILL BE ONE MORE WATER CLOSET REQ-
 UIRED MINIMUM. IF ADDED TO THE MENS
 TOILET ROOM THEN POTTY PARITY IS NOT
 BEING ADDRESSED.
 2) SHT ME2 HAS NOT CHANGED. INFORMATION
 HAS BEEN TRANSFERRED TO SHT ME1 AND ME2
 STILL HAS INCORRECT WATER RISER. A NEW
 SHEET SP-1 HAS BEEN ADDED FOR INFORMAT-
 ION PREVIOUSLY ON SHT ME1. PLEASE
 CLAIRFY, AS THE INFORMATION CAN NOT BE
 APPROVED.
 3) ENGINEERS NAME AND LICENSE NUMBER
 MISSING FROM SHTS ME2 AND SP-1.
 61G15-23.002(2) & FS 471
  