2004-01-06 00:00:00DENIED:
 PLEASE NOTE THE VAULT ROOM IS INDICATED
 AS A 3 HR FIRE RESISTANCE RATING.FIRE
 DAMPERS ARE NOT INDICATED AT THE WALL
 PENETRATION OR CEILING PENETRATIONS.
 PLEASE CLARIFY.
  