Plan Review Notes
Plan Review Notes For Permit 03090979
Permit Number 03090979
Review Stop E
Sequence Number 2
Notes
Date Text
2004-01-02 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SUBMIT/SHOW THE GROUNDING
 ELECTRODE SYSTEM PER 250.50 BLDG/FOOTER/
 CWP ETC. FIRST REVIEW NOTE.
  
 2)NOTE: PLEASE SHOW/CLARIFY EQUIPMENT
 GROUNDING BETWEEN MAINAND GUTTER AND
 GUTTER AND PANELS. 250.110, 250.24, SIZE
 PER 250.122
  
 3)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN. NOTE MENTIONS FPL FAULT CURRENT
 AND PANELS ARE SHOWN WITH BRANCH BRKRS
 RATED AT 42K. 110.9/215.5
  
 4)NOTE: RISER SHOWS PARALLEL RUNS TO
 METER YET NOT FROM METER TO MAIN AND
 GUTTER. PLEASE CLARIFY. SAME CONDUCTORS
 ETC ARE CARRIED THROUGH.
  
 PLEASER SEE PLANS ARE COMING BACK FOR
 FIRE REIVEW COMMENTS. PLEASE SEE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  