Date |
Text |
2004-01-16 00:00:00 | SECOND CHECKLIST |
| ARCHITECTUAL PLANS DATED 12/22/03 AND |
| STRUCTURAL PLANS DATED 12/19/03. |
| |
| THE PREVIOUSLY REQUESTED SURVEY AND SITE |
| PLAN HAVE NOT BEEN PROVIDED.SHEET 2.1 |
| TITLED SITE PLAN, DOES NOT HAVE ANY |
| HORIZONTAL CONTROL DIMENSIONS TO LOCATE |
| THE BUILDING OR ANYTHING ELSE ON THE |
| PROPERTY.PROPERTY LINES ARE NOT |
| IDENTIFIED. SECTION 2, ON SHEET 2.1 |
| SHOWS A SITE WALL DETAIL WITH THE NOTE |
| THAT THE FF ELEV.IS 27.25' NGVD.IS |
| THIS OF RELEVANCE TO THE SITE WALL? |
| |
| 2THE ARCHITECT'S RESPONSE LETTER |
| DATED 12/22/03 STATES THAT A "FIRE |
| RISERSCHEMATIC" CAN BE FOUND ON REVISED |
| SHEET ME2. SHEET ME2 DATED 12/19/03 |
| FROMCHANE, INC. HAS NO FIRE SPRINKLER |
| DESIGN INFORMATION ON IT. |
| |
| 3RESPONSE #3 OF THE ARCHITECT'S |
| LETTERSTATES THAT THE ATTIC SPACE WILL |
| HOUSE MECHANICAL EQUIPMENT, SEE SHEET |
| M1 NOTE 5A FOR GRAVITY LOADS.SHEETS |
| M1 AND M2 ARE BEREFT OF ANY NOTES. |
| |
| 4ARCHITECTS RESPONSE #5 RE: THE |
| OUTDATED CODE STANDARDS TO REFER TO |
| REVISED SHEET S3.THE S3 SHEET STILL |
| CONTAINS ERRONEOUS AND OUTDATED |
| INFORMATION.IT IS PARTICULARLY |
| TROUBLESOME TO ME THAT A PROFESSIONAL |
| ENGINEER USES AN OUDATED PRESCRIPTIVE |
| RESIDENTIAL DESIGN FOR A COMMERCIAL |
| BUILDING. |
| |
| 5THE PREVIOUS REQUEST FOR HIGH LIFT |
| GROUTING HAS NOT BEEN ADDRESSED.SHEET |
| S3 REFERS TO SPECIFICATIONS THAT WERE |
| NOT FOUND. |
| |
| 6COLUMNS SHOWN AS MC1 ARE NOT IN THE |
| COLUMN SCHEDULE ON SHEET S3.IS THE |
| 12/22/03 LETTER FROM THE ARCHITECT |
| INTENDED TO BE MADE A PART OF THE |
| PERMIT PLANS SINCE THOSE RESPONSES HAVE |
| SOME OF THE INFORMATION THAT IS ABSENT |
| FROM THE PLANS? |
| |
| 7THE REQUESTED COLUMN CONNECTIONS FOR |
| THE TS COLUMNS SHOWN ON SHEETS S1 AND |
| S2 HAVENOT BEEN PROVIDED. |
| |
| 8SHEET S3 ROOF WIND ZONE SKETCH.DID |
| THE ENGINEER USE THE SIMPLIFIED METHOD |
| IN ASCE 7-98 SECTION 6.4 OR THE |
| ANALYTICAL METHOD IN SECTION 6.5?IN |
| EITHER CASE, HOW WERE EDGE AREAS OF 4' |
| AND 5' DETERMINED FOR A BUILDING WITH A |
| LEAST DIMENSION OF 73' AND A MEAN ROOF |
| HEIGHT OF 16.5'?WHERE ARE ZONES 4&5? |
| |
| 9SEE FBC 13-400.3 FOR COMPUTER BASED |
| ENERGY CALCULATIONS AND THE ATTENDANT |
| METHODS TO BE USED.ALSO, THE 6020 SF |
| GROSS AREA INPUT DOES NOT AGREE WITH |
| THE PLANS' 6700 + SQUARE FEET |
| CONDITIONED AREA.PLEASE REVISE AS |
| NECESSARY. |
| |
| 10THE IMPACT FEES AND NOA'S CALLED OUT |
| IN THE FIRST CHECKLIST REMAIN |
| APPLICABLE. |