2004-01-16 00:00:00SECOND CHECKLIST
 ARCHITECTUAL PLANS DATED 12/22/03 AND
 STRUCTURAL PLANS DATED 12/19/03.
  
 THE PREVIOUSLY REQUESTED SURVEY AND SITE
 PLAN HAVE NOT BEEN PROVIDED.SHEET 2.1
 TITLED SITE PLAN, DOES NOT HAVE ANY
 HORIZONTAL CONTROL DIMENSIONS TO LOCATE
 THE BUILDING OR ANYTHING ELSE ON THE
 PROPERTY.PROPERTY LINES ARE NOT
 IDENTIFIED. SECTION 2, ON SHEET 2.1
 SHOWS A SITE WALL DETAIL WITH THE NOTE
 THAT THE FF ELEV.IS 27.25' NGVD.IS
 THIS OF RELEVANCE TO THE SITE WALL?
  
 2THE ARCHITECT'S RESPONSE LETTER
 DATED 12/22/03 STATES THAT A "FIRE
 RISERSCHEMATIC" CAN BE FOUND ON REVISED
 SHEET ME2. SHEET ME2 DATED 12/19/03
 FROMCHANE, INC. HAS NO FIRE SPRINKLER
 DESIGN INFORMATION ON IT.
  
 3RESPONSE #3 OF THE ARCHITECT'S
 LETTERSTATES THAT THE ATTIC SPACE WILL
 HOUSE MECHANICAL EQUIPMENT, SEE SHEET
 M1 NOTE 5A FOR GRAVITY LOADS.SHEETS
 M1 AND M2 ARE BEREFT OF ANY NOTES.
  
 4ARCHITECTS RESPONSE #5 RE: THE
 OUTDATED CODE STANDARDS TO REFER TO
 REVISED SHEET S3.THE S3 SHEET STILL
 CONTAINS ERRONEOUS AND OUTDATED
 INFORMATION.IT IS PARTICULARLY
 TROUBLESOME TO ME THAT A PROFESSIONAL
 ENGINEER USES AN OUDATED PRESCRIPTIVE
 RESIDENTIAL DESIGN FOR A COMMERCIAL
 BUILDING.
  
 5THE PREVIOUS REQUEST FOR HIGH LIFT
 GROUTING HAS NOT BEEN ADDRESSED.SHEET
 S3 REFERS TO SPECIFICATIONS THAT WERE
 NOT FOUND.
  
 6COLUMNS SHOWN AS MC1 ARE NOT IN THE
 COLUMN SCHEDULE ON SHEET S3.IS THE
 12/22/03 LETTER FROM THE ARCHITECT
 INTENDED TO BE MADE A PART OF THE
 PERMIT PLANS SINCE THOSE RESPONSES HAVE
 SOME OF THE INFORMATION THAT IS ABSENT
 FROM THE PLANS?
  
 7THE REQUESTED COLUMN CONNECTIONS FOR
 THE TS COLUMNS SHOWN ON SHEETS S1 AND
 S2 HAVENOT BEEN PROVIDED.
  
 8SHEET S3 ROOF WIND ZONE SKETCH.DID
 THE ENGINEER USE THE SIMPLIFIED METHOD
 IN ASCE 7-98 SECTION 6.4 OR THE
 ANALYTICAL METHOD IN SECTION 6.5?IN
 EITHER CASE, HOW WERE EDGE AREAS OF 4'
 AND 5' DETERMINED FOR A BUILDING WITH A
 LEAST DIMENSION OF 73' AND A MEAN ROOF
 HEIGHT OF 16.5'?WHERE ARE ZONES 4&5?
  
 9SEE FBC 13-400.3 FOR COMPUTER BASED
 ENERGY CALCULATIONS AND THE ATTENDANT
 METHODS TO BE USED.ALSO, THE 6020 SF
 GROSS AREA INPUT DOES NOT AGREE WITH
 THE PLANS' 6700 + SQUARE FEET
 CONDITIONED AREA.PLEASE REVISE AS
 NECESSARY.
  
 10THE IMPACT FEES AND NOA'S CALLED OUT
 IN THE FIRST CHECKLIST REMAIN
 APPLICABLE.