Plan Review Notes
Plan Review Notes For Permit 03090979
Permit Number 03090979
Review Stop P
Sequence Number 1
Notes
Date Text
2003-10-15 00:00:00DENIED
 REFERENCE: FBC-2001 BUILDING
 FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) PROVIDE CALCULATIONS FOR MINIMUM
 FIXTURE FACILITIES PER TABLE 403.1
 PLUMBING AND TABLE 1003.1 BUILDING.
 SHOW SQUARE FOOTAGE FOR EACH OCCUPANCY
 OF THE BUILDING, ASSEMBLY, BUSINESS, &
 STORAGE.
 2) SECTION 4.3.1.1 IN ASSEMBLY OCCUPAN-
 CIES, RESTROOMS WHICH ARE OPEN TO THE
 PUBLIC MUST HAVE A RATIO OF 3 TO 2 W/C'S
 PROVIDED FOR WOMEN AS THE COMBINED TOTAL
 OF W/C'S AND URNALS PROVIDED FOR MEN. AS
 IT SHOWN, A MINIMUM OF 5 W/C'S WILL BE
 REQUIRED FOR WOMEN. (3 X 1.5 = 4.5 ROUND
 UP TO 5).
 3) SHT ME2 WATER ISOMETRIC, AIR CHAMBERS
 ARE NOT APPROVED. SECTION 604.9
 DELETE AIR CHAMBERS FROM ISOMETRIC.
  