Plan Review Notes For Permit 03090979 |
Permit Number |
03090979 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-15 00:00:00 | DENIED | | REFERENCE: FBC-2001 BUILDING | | FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | | | 1) PROVIDE CALCULATIONS FOR MINIMUM | | FIXTURE FACILITIES PER TABLE 403.1 | | PLUMBING AND TABLE 1003.1 BUILDING. | | SHOW SQUARE FOOTAGE FOR EACH OCCUPANCY | | OF THE BUILDING, ASSEMBLY, BUSINESS, & | | STORAGE. | | 2) SECTION 4.3.1.1 IN ASSEMBLY OCCUPAN- | | CIES, RESTROOMS WHICH ARE OPEN TO THE | | PUBLIC MUST HAVE A RATIO OF 3 TO 2 W/C'S | | PROVIDED FOR WOMEN AS THE COMBINED TOTAL | | OF W/C'S AND URNALS PROVIDED FOR MEN. AS | | IT SHOWN, A MINIMUM OF 5 W/C'S WILL BE | | REQUIRED FOR WOMEN. (3 X 1.5 = 4.5 ROUND | | UP TO 5). | | 3) SHT ME2 WATER ISOMETRIC, AIR CHAMBERS | | ARE NOT APPROVED. SECTION 604.9 | | DELETE AIR CHAMBERS FROM ISOMETRIC. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|