2003-10-10 00:00:00 | DENIED: | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | AS PER 2001 FBC(M) 606.2.1 WITH | | NOTIFICATION TO ALARM/STROBE IN | | NORMALLY OCCUPIED AREAS AS PER NFPA 90A | | 4-4.4.3. | | | | ROOF STANDS FOR THE CONDENSING UNITS | | SHALL COMPLY WITH 2001 FBC 1511.7 SEE | | ATTACHED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|