2003-10-10 00:00:00DENIED:
 FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 AS PER 2001 FBC(M) 606.2.1 WITH
 NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER NFPA 90A
 4-4.4.3.
  
 ROOF STANDS FOR THE CONDENSING UNITS
 SHALL COMPLY WITH 2001 FBC 1511.7 SEE
 ATTACHED.
  