Plan Review Notes
Plan Review Notes For Permit 03090979
Permit Number 03090979
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2003-09-19 00:00:001) NO FIRE SPRINKLER PLANS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 DRAWINGS. THE CODE SUMMARY BOX
 INDICATES THAT THE BUILDING WILL BE
 FIRE SPRINKLER PROTECTED.
  
 2) PLEASE INDICATE THE PROPOSED OCCUPANT
 LOAD FOR THE BUILDING.
  
 3) PANIC HARDWARE IS REQUIRED ON
 EXIT DOORS IF 100 OR MORE PERSONS
 ARE EXPECTED.
  
 4) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 5) THE ACCORDIAN FOLDING PARTITION IS
 COMPRISED OF WHAT CONSTRUCTION.
  
 6) BUILDING ADDRESS IS REQUIRED ON
 PROPER ELEVATION. A MINIMUM OF 6"
 NUMBERS ARE REQUIRED.
  
 7) AT LEAST TWO OF THE DOORS APPEAR
 TO SWING TOO FAR INTO THE CORRIDOR.
 PLEASE EXPLAIN RATIONALE.
  
 8) PLEASE ENSURE THAT ALL FIRE SAFETY
 EQUIPMENT AND OR DEVICES ARE SHOWN
 ON THE PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910