Plan Review Notes For Permit 03090979 |
Permit Number |
03090979 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-19 00:00:00 | 1) NO FIRE SPRINKLER PLANS OR | | HYDRAULIC CALCULATIONS PROVIDED WITH | | DRAWINGS. THE CODE SUMMARY BOX | | INDICATES THAT THE BUILDING WILL BE | | FIRE SPRINKLER PROTECTED. | | | | 2) PLEASE INDICATE THE PROPOSED OCCUPANT | | LOAD FOR THE BUILDING. | | | | 3) PANIC HARDWARE IS REQUIRED ON | | EXIT DOORS IF 100 OR MORE PERSONS | | ARE EXPECTED. | | | | 4) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | 5) THE ACCORDIAN FOLDING PARTITION IS | | COMPRISED OF WHAT CONSTRUCTION. | | | | 6) BUILDING ADDRESS IS REQUIRED ON | | PROPER ELEVATION. A MINIMUM OF 6" | | NUMBERS ARE REQUIRED. | | | | 7) AT LEAST TWO OF THE DOORS APPEAR | | TO SWING TOO FAR INTO THE CORRIDOR. | | PLEASE EXPLAIN RATIONALE. | | | | 8) PLEASE ENSURE THAT ALL FIRE SAFETY | | EQUIPMENT AND OR DEVICES ARE SHOWN | | ON THE PLANS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|