Plan Review Notes For Permit 03090979 |
Permit Number |
03090979 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-10-07 00:00:00 | ************** UNSAT *************** | | | | 1)NOTE: PLEASE CORRELATE ALL CIRCUITING | | ON PLANS WITH PANEL SCHEDULES. | | THERE ARE A SOME CIRCUITS THAT DO NOT | | CORRELATE,SEE A COUPLE OF CIRCUITS SHOWN | | ON PLAN AND NOT ON PANEL SCHEDULE. | | | | 2)NOTE; PLEASE CORRELATE RISER AND PANEL | | (S). PANEL S IS TETC. | | PLEASE CORRECT CONDUCTOR SIZES ACCORD. | | TO PANEL. | | | | 3)NOTE: PLEASE SEE THAT PANEL "T" IS | | SHOWN HAVING NO NEUTRAL, HOWEVER THE | | NEUTRAL IS REQ'D TO TERMINATE IN PANEL | | EVEN IF IT IS GOING TO USED. | | | | 4)NOTE: PLEASE SEE THAT THERE IS NO | | GROUNDING ELECTRODE SYSTEM SHOWN? | | PLEASE SEE 250.50/250.66 | | | | 5)NOTE: PLEASE SEE TOTAL AMPS SHOWN FOR | | "C" PHASE ON PANEL "S". 9595A'S | | | | 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | MAIN ETC. 110.9 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. 215.5 IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|