Date Text
2003-10-07 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH PANEL SCHEDULES.
 THERE ARE A SOME CIRCUITS THAT DO NOT
 CORRELATE,SEE A COUPLE OF CIRCUITS SHOWN
 ON PLAN AND NOT ON PANEL SCHEDULE.
  
 2)NOTE; PLEASE CORRELATE RISER AND PANEL
 (S). PANEL S IS TETC.
 PLEASE CORRECT CONDUCTOR SIZES ACCORD.
 TO PANEL.
  
 3)NOTE: PLEASE SEE THAT PANEL "T" IS
 SHOWN HAVING NO NEUTRAL, HOWEVER THE
 NEUTRAL IS REQ'D TO TERMINATE IN PANEL
 EVEN IF IT IS GOING TO USED.
  
 4)NOTE: PLEASE SEE THAT THERE IS NO
 GROUNDING ELECTRODE SYSTEM SHOWN?
 PLEASE SEE 250.50/250.66
  
 5)NOTE: PLEASE SEE TOTAL AMPS SHOWN FOR
 "C" PHASE ON PANEL "S". 9595A'S
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 MAIN ETC. 110.9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. 215.5 IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  