2003-10-21 00:00:00PLEASE PROVIDE A RECENT PROPERTY SURVEY
 AND A SITE PLAN WITH DIMENSIONS LOCATING
 THE PROPOSED BUILDING ON THE PROPERTY.
 SEE FBC 104.2.4.
  
 PLEASE SHOW THE FIRE PROTECTION SYSTEMS
 ON THE PLANS, INCLUDING SPRINKLER
 DESIGN. SEE FBC 104.3.1.1.
  
 SHEET S2.WHAT WILL THE ATTIC SPACE BE
 USED FOR AND WHAT ARE THE DESIGN LIVE
 AND DEAD LOADS?
  
 WHAT WILL THE VAULT SHOWN ON SHEET 3.1
 BE USED FOR?
  
 THE STANDARDS CITED ON SHEET S3, LIKE
 ACI, ARE NOT THE EDITIONS INVOKED BY
 THE FBC.SEE FBC 3501 AND REVISE AND
 DEMONSTRATE COMPLIANCE AS NECESSARY.
  
 PLEASE PROVIDE THE SPECIFICATION FOR THE
 HIGH LIFT GROUTING CALLED OUT IN NOTE
 J(3) ON S3.
  
 NOTE P3 ON S3 CITES SSTD 10-97 WHICH IS
 NEITHER CURRENT OR APPLICABLE TO THIS
 BUILDING FOR DESIGN OF THE ROOF
 DIAPHRAGM SYSTEM.PLEASE REVISE AND
 DEMONSTRATE COMPLIANCE WITH FBC 2310.
 (DO NOT QUOTE CODE SECTIONS)
  
 THE DOORS SHOWN AS 110 & 111 AND 108
 ON SHEET 3.1, SWINGING INTO CORRIDORS
 109 AND 106 RESPECTIVELY, ARE
 PROHIBITTED BY FBC 1012.1.4.
  
 THE WINDOW SCHEDULE AND SHEET 10.1
 DECLARES A DESIGN WIND SPEED OF 110
 MPH.THECITY OF WEST PALM BEACH IS IN
 A 140 MPH WIND ZONE.PLEASE REVISE AS
 NECESSARY.
  
 THE ROOF ZONE SKETCH ON SHEET S3 IS NOT
 CLEAR.SEE ASCE 7-98 TABLE 6-5B.WHERE
 ARE THE WALL PRESSURES ZONES 4 & 5 ?
 WHAT IS THE BASE VELOCITY PRESSURE?
 HOW WERE THE DOOR AND WINDOWS PRESSURES
 SHOWN DETERMINED?
  
 SHEET S3 SECTION 5, PLEASE SPECIFY THE
 WELDS TO USED FOR THE HURRICANE STRAPS.
  
 SHEET S2, HOW IS THE W 10X22 CONNECTED
 TO THE MC 1 COLUMN?WHERE IS SECTION
 11/10.3 FOUND?
  
 MC 1 IS NOT SHOWN ON THE COLUMN
 SCHEDULE.
  
 SHOW THE ATTIC ACCESS AND ATTIC
 VENTILATION IN ACCORDANCE WITH FBC
 2309.6 AND 2309.7.ALSO SHOW THE FREE
 AREA CALCULATION AND NOTE WHETHER THE
 LATH FREE AREA TOGETHER WITH THE SCREEN
 AREA HAS BEEN USED.
  
 SHOW THE COLUMN CONNECTIONS, TOP AND
 BOTTOM, FOR THE STEEL COLUMNS DEPICTED
 ON SHEET S.2.
  
 SHEET 8.1, SHOW THE FIRE BLOCKING AS
 PROVIDED FOR IN FBC 705.3.1.1 FOR THE
 CHASEWALL SHOWN AS [D], OR THE FIRE
 STOPPING METHOD.
  
 THE ENERGY CODE INPUT DATA SHEET SHOWS
 VALUES FOR THE ROOF CONSTRUCTION
 MATERIAL.FBC 13-404.1ABCD REQUIRES
 THE CEILING TO BE USED WHEN THERE IS A
 VENTED CAVITY.PLEASE REVISE AS
 NECESSARY.
  
 IF TEST REPORTS AND/OR NOA'S FOR THE
 DOORS, WINDOWS AND ROOF COVERING ARE
 NOT INCLUDED WITH THE PERMIT
 APPLICATION, SEPARATE PERMIT(S), FEES
 AND INFORMATION WILL BE REQUIRED.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL (561) 233-5025 FOR
 MORE INFORMATION.