Plan Review Notes
Plan Review Notes For Permit 03090799
Permit Number 03090799
Review Stop P
Sequence Number 1
Notes
Date Text
2003-10-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) 61G15-23.002(1) 2 SETS OF PLANS HAVE
 NO SEAL, SIGNATURE, OR DATE ON THEM.
 61G15-23.002(2) LICENSE NOT SHOWN ON THE
 TITLE BLOCK AS REQUIRED.
 2) 11-4.1.6(1)(B) IF EXISTING ELEMENTS,
 SPACES, OR COMMON AREAS ARE ALTERED,
 THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF 11-4.1.1 TO
 11-4.1.3. SO PER 11-4.1.3, IF TOILET
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH
 11-4.22. SUBMIT A DETAIL SHOWING COMPLI-
 ANCE WILL 11-4.22, 11-4.16, & 11-4.19
 AND ALL SUBSECTIONS OF EACH. - ALSO SEE
 SECTION 3401.8.1.1 (BLDG)
 3) THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IS MEET
 CODE REQUIREMENTS. 909.1 W/M SHALL NOT
 DRAIN INTO THE HORIZONTAL WET VENT OF
 THE BATHROOM GROUP OF FIXTURES. 708.10
 WASH MACHINE STACK SHALL HAVE A CLEANOUT
 4' ABOVE THE FLOOR.SEE ATTACHED RISER
 FOR AN EXAMPLE OF A RISER THAT MEETS
 CODE REQUIREMENTS AND REFLECTS THE FLOOR
 PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]