2003-09-24 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| TO THE PLANS AND RESUBMIT FOR REVIEW. |
| |
| 1} THE LOAD CALCULATIONS SUBMITTED ARE |
| FOR DWELLING UNITS. PLEASE SUBMIT |
| CALCULATIONS AND PANEL SCHEDULES FOR |
| THE COMMERCIAL APPLICATION BEING |
| APPLIED PER 220.3. |
| |
| 2} PLEASE LABEL CIRCUITS ON THE FLOOR |
| PLAN AND CORRELATE WITH THE PANEL |
| SCHEDULE. |
| |
| 3} PLEASE NOTE THAT THE RECEPTACLES IN |
| CLIENT AREAS MUST COMPLY WITH 16.5.1.2 |
| NFPA-72. |
| |
| 4} PLEASE NOTE THAT ALL PLANS |
| DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- |
| ING A TITLE BLOCK, MUST BE SIGNED, |
| DATED AND SEALED BY THE ARCH/ENGINEER OF |
| RECORD. PER FS/FAC 481.221 & 471.025 |
| |
| 5} THE SMOKE DETECTOR IN THE KITCHEN IS |
| IN VIOLATION OF 8-1.4.2 NFPA-72.MUST BE |
| A LISTED HEAT DETECTOR OR REMOVED. |
| |
| NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW EQUIPMENT BEING INSTALLED. |
| MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT PER 110.9, |
| IF ANY SERVICE EQUIPMENT IS BEING |
| ADDED OR REPLACED. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |