Plan Review Notes
Plan Review Notes For Permit 03090799
Permit Number 03090799
Review Stop E
Sequence Number 1
Notes
Date Text
2003-09-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE LOAD CALCULATIONS SUBMITTED ARE
 FOR DWELLING UNITS. PLEASE SUBMIT
 CALCULATIONS AND PANEL SCHEDULES FOR
 THE COMMERCIAL APPLICATION BEING
 APPLIED PER 220.3.
  
 2} PLEASE LABEL CIRCUITS ON THE FLOOR
 PLAN AND CORRELATE WITH THE PANEL
 SCHEDULE.
  
 3} PLEASE NOTE THAT THE RECEPTACLES IN
 CLIENT AREAS MUST COMPLY WITH 16.5.1.2
 NFPA-72.
  
 4} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 5} THE SMOKE DETECTOR IN THE KITCHEN IS
 IN VIOLATION OF 8-1.4.2 NFPA-72.MUST BE
 A LISTED HEAT DETECTOR OR REMOVED.
  
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9,
 IF ANY SERVICE EQUIPMENT IS BEING
 ADDED OR REPLACED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718