2003-09-17 00:00:00 | ************ UNSAT ******************* | | | | 1)NOTE: PLEASE CLARIFY IF THERE A MAIN | | W/ THE METER. PLEASE SHOW IF METER/MAIN | | COMBO. PLANS ONLY INDICATE METER? | | | | 2)NOTE: PLEASE SEE THAT SD'S ARE MISSING | | INSIDE AND OUT ALL BED RMS. SD OUTSIDE | | BD RM #3 WOULD NOT BE REQ'D HOWEVER | | WOULD STILL BE REQ'D TO WIRED INLINE. | | NFPA-72 8-1.4.2 | | | | 3)NOTE: PLEASE SEE MISSING RECEPTS PER | | 210.52. REDLINED ON ONE SET OF E-SHEETS | | | | 4)NOTE: PLEASE CLARIFY WHAT APPEARS TO | | BE DOORS FROM LIVING RM TO OUTDSIDE? | | PLEASE SEE MISSING CONTROL FOR EGRESS | | LIGHTING PER 210.70 AND LS 101. 5-8 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|