2003-09-17 00:00:00DENIED:
 1. RETURN AIR REQUIRED FROM THE OFFICE
 AREA.
 2. RETURN AIR DUCT TO THE MBR, DUCT
 SIZE NOT INDICATED.
 3. RETURN AIR REQUIRED FROM BR2.
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  