Notes
Date Text
2003-09-17 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 THE GEC MUST BE INSTALLED #2 CU PER 210.
 66.
  
 THE BATH CIRCUITS MUST BE INSTALLED PER
 210.11(C)(3),#12 ON A 20A CIRCUIT(S).
  
 NOTE THAT PER 210.12 ALL BRANCH CIRCUITS
 ~~~~~~~~SHALL BE PROTECTED BY ARC FAULT
 CIRCUIT INTERRUPTER.THAT INCLUDES LIGHT
 OUTLETS AND SMOKE DETECTORS AS WELL AS
 RECEPTACLES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW