Plan Review Notes For Permit 03090351 |
Permit Number |
03090351 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-09-17 00:00:00 | PROVISO | | ~~~~~~~ | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | | THE GEC MUST BE INSTALLED #2 CU PER 210. | | 66. | | | | THE BATH CIRCUITS MUST BE INSTALLED PER | | 210.11(C)(3),#12 ON A 20A CIRCUIT(S). | | | | NOTE THAT PER 210.12 ALL BRANCH CIRCUITS | | ~~~~~~~~SHALL BE PROTECTED BY ARC FAULT | | CIRCUIT INTERRUPTER.THAT INCLUDES LIGHT | | OUTLETS AND SMOKE DETECTORS AS WELL AS | | RECEPTACLES. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 |
|