Plan Review Notes For Permit 03090340 |
Permit Number |
03090340 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2003-12-30 00:00:00 | PROVISO: | | 1.CONDENSING UNIT STAND SHALL COMPLY | | WITH 2001 FBC 1511.7 FOR THE CLEARANCE | | BETWEEN THE ROOF SURFACE AND THE BOTTOM | | OF THE SUPPORT RAIL OF THE STAND. | | | | 2.RETURN AIR DUCT IS NOT SIZED.SHOW | | COMPLIANCE WITH REVISION TO THE 2001 | | FBC(M) 601.4 #1.DUCTS SHALL BE SIZED | | PRIOR TO INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|